Basic Info
Model NO.: XGN-12
Structure: Fixed Board
Form: All- packaged Type
Size: 1 Uint
Shell Material: Stainless Steel
Specification: IEC
HS Code: 8504
Type: Distribution Metering Box
Certification: ISO9001:2000
Operation Voltage: Low Voltage
Application Range: Power Plants
Shell Protection Grade: IP55
Test: Type Test Report
Transport Package: Wooden Cases
Origin: China
Product Description
XGN-12 Box Type Fix Type AC RMU Switchgear (side install type) (following abbreviation switch ) is used in 10kV three-phase AC 50Hz indoor system as accepting and distributing electric energy, especially suitable in the occasion of frequently operates. The bus system is one bus. This switch fits the requirement of national standard GB39063~35kV's AC metal closed switch and IEC298, and possesses tightly the shutting meritability of "five guards "This switch apparatus has been surmounted old type fixed switchgear's defects such as the switch volume is huge and the maintenance is not convenience, etc. And has surmounted moving out type switchgear's defects of complicated handcart organization, once connection the protection operation organization is unreliable, etc. It is a new small model fix type switchgearof researching and developing by self.
Reliable electrically connection.
Convenient examined and repaired.
Installation of once cable can be accomplished before the cupboard.
Product can be installed by the wall.
Use the isolation switch and ground connection switch operation organization and interlock device of integrationization design, the operates and interlock is convenient and reliable.
Once component is vertial range.
The breaker room, bus room and cable room have leak pressure channel.
The frame is combined by applying aluminium zinc board,
It is the smallest volume in the fixed switch of double disconnection switch in the internal: Wide X deep X height = 750 X1100 X2100mm.
1. Mechanism compartment7. Cable compartment
2. Pressure meter and inflation/deflation device8. Cable bushing
3. Disconnector operating mechanism9. Current (voltage) transformer
4. Circuit breaker operating mechanism (permanent magnetic)11. Three-position disconnector
5. Vacuum arc-extinguishing chamber10. Gas insulated insulator
6. Lower control box12. Pressure release device
Item | Unit | Parameter | |
Rated voltage | kV | 12&35&40.5 | |
Rated current | A | 630 1250 2000 2500 | |
Rated frequency | Hz | 50 | |
Rated power frequency withstand voltage (1min) | Phase to phase, Phase to earth | kV | 42 |
Insulation Distance | 48 | ||
Rated Lightning impulse withstand voltage | Phase to phase, Phase to earth | kV | 75 |
Insulation Distance | 85 | ||
1min power frequency withstand voltage of Auxiliary control circuit | V | 2000 | |
Rated short-circuit breaking current (effective value) | kA | 25 31.5 40 | |
Rated short time withstand current | kA /s | 25/4 31.5/4 40/4 | |
Rated peak withstand current | kA | 63 80 100 | |
Rated short-circuit making current | kA | 63 80 100 | |
Every phase main return circuit resistance | μΩ | ≤250 | |
Rated SF6 gas pressure (20oC) | Mpa | 0.045±0.005 | |
Min SF6 gas pressure (20oC) | Mpa | 0.03 | |
Annual SF6 gas loss rate | % | ≤1 | |
Rated voltage of auxiliary control circuit | V | DC110/220,AC220 | |
Degrees of protection | Gas-filled compartment:IP67 Low-voltage compartment:IP4X | ||
Dimensions (Width×Depth×Height) | mm | 500 ×1000×1850 |