Home > Knowledge > Content

11kv 33kv Power Distribution Cabinet High Voltage Metal Clad Switchgear

Jun 20, 2017

Basic Info

  • Shell Material: Steel Plate

  • Structure: Cabinet, Protection

  • Type: Power

  • Operation Voltage: High Voltage

  • Application Range: Power Plants

  • Brand: Shanghai Electric

  • Specification: type tested

  • HS Code: 85372090

  • Certification: CCC, ISO9001:2000, Type Tested

  • Voltage Level: High Voltage

  • Item: Metal Clad Switchgear

  • Form: Partly-welded Type

  • Size: 1 Uint

  • Shell Protection Grade: IP30

  • Origin: China


Product Description


Summary:
 
medium volage metal clad switchgear is three -phase AC50Hz,rated voltage 24KV indoor power distribution equipment .As power plants ,substations ,industrial &mining enterprises to accept amd distribute of electric energy to control ,protect and monitor ,circuit ,ect.Can also be used to control the place of frequent operation .
 
Structure Description:
 
Switchgear are requested designed according to GB3906 and IEC 298.The whole switchgear can be extracted from the cabinet and spare parts (trolley) two components ,Cabinet structure are made of aluminum deposited zine plate or galvanized plate bolted combination forming a metal partition separationg the part of the circut break room,main busbar room cable room and relay control room.and all metal construction were grounded ,each com-partment of the main circuit system has separste pressure release channel,In the cable compartment can be set to 40*6mm ground busbar .
 
Main characteristics:
simple and effective 'Five Anti'lockout to prevent misuse
Can be equipped with VS1.VD4,3AH vacuum contactors ,etc
Can be equipped with voltage transformer hancart,isolation handcart,fuses ,ect,Used ,Used same use interchangeable .
The switch cabinet can be wall mounted ,front cabinet maintenance ,reduce floor space .
The circuit breaker compartment and cable compartment heater can be installed separately ,to prevent condenstation and corrosion ;
Cable ample room space,can be connected to a plurality of cables .
Shell protection grade IP4*,among compartment protection class IP2*:
The meterial can be gavanized sheet can be deposited aluminum and zinc plate production .
Cabinet outline dimensions(mm)(not including door)

         Height        Width         Depth
          2300        800         1800
          2300        1000         1800

 
 
Advantages:
good compatibility, stable and reliable performance, free maintenance and long service life, is old-fashioned contactor is the ideal substitute of products.
 

Place of Origin:China (Mainland)Brand Name:OEMModel Number:KYN28
12/24KV swichgear:metal-clad enclosed switchgearrated current:630~2000Arated current of dynamic stability (4S):16/20/25/31.5/40/50KA
Protection degree.:IP2X&IP4X




KYN28 Metalclad AC Indoor Enclosed Switchgear,Withdrawable type

 
1. General Description
 
1.1 Application: In the power system of 3.6  to 24kV, for control, protection and monitoring.VCBs produced
 
by us or VCBs produced by other manufactures could be installed in the switchgear panel.
 
1.2 Standards : IEC 62271-200
 
1.3 Parameters: Rated voltage: 12/24KV
 
1.4 Rated current: 630-5000A
 
1.5 Rated short-circuit breaking current: 16kA-31.5kA

 
2.Features:
 
2.1.Compact design
 
2.2.Easy operation and installation
 
2.3.Reliable interlock
 
2.4.Less Maintenance
 

3.Technical Data
 

No.ItemUnitData
3.1Rated voltagekV3.6,7.2,12
3.2Rated current of circuit breakerA630,1250,1600,2000,2500,3150,4000,5000
Rated current of switchgearA630,1250,1600,2000,2500,3150,4000,5000
3.3Rated frequencyHz50
3.4
 
Rated short-circuit breaking currentkA16,20,25,31.5,40,50
Rated short-time withstand currentkA16,20,25,31.5,40,50
Rated short circuit continuous times4
3.5Rated peak withstand currentkA40,50,63,80,100,125
Rated short-circuit closing current(peak)kA40,50,63,80,100,125
3.6Rated insulation level: 1min power frequency withstand voltagekV24,32,42 between poles, pole to earth
kV24,32,48 between open contacts
3.7Rated insulation level: Lighting impulse withstand voltage(peak)kV40,60,75 between poles, pole to earth
kV46,70,85 between open contacts
3.8Rated power frequency withstand voltagekV95/1min
3.9Protection levelSwitchgear shell IP3X
Compartments(door opened) IP2X when the CPT and CB doors are open.

 
Note: 1.The short circuit capacity of the current transformer should be separately considered.
 
    2. See technical parameters of ZN63A(VS1)-12 in related product of our company.